沼气进入塔体的底部,并从底部到顶部穿过填料层。通过变频控制准确添加空气。尾气成分分析仪监测沼气出口的氧气浓度,并与鼓风机一起工作。
The biogas enters the bottom of the tower and passes through the filling layer from bottom to top. Accurately add air through variable frequency control. The exhaust gas composition analyzer monitors the oxygen concentration at the biogas outlet and works together with the blower.
空气供应量大小由进入沼气气体流量信号精确控制, 使得氧气占到混合气体的百分比控制在一定范围,可保证不会因设计或供货缺陷造成事故。同时空气系统的设定向罐体内通入空气,如果空气量不足,脱硫效果会快速降低。根据脱硫系统的负荷,通过一个变频器调节风机的转速。在脱硫系统的后面安装氧气传感器作为控制空气通入量的保障。在正常运行过程中,出气中氧气剩余含量为 1.5~2.0%。如果沼气中氧气含量超过 1.75%,风机转速将会降低,如果达到 2.5%,风机将会停止。此值可设定。
The size of the air supply is precisely controlled by the flow signal of the entering biogas gas, so that the percentage of oxygen in the mixed gas is controlled within a certain range, ensuring that safety accidents will not be caused by design or supply defects. At the same time, the safety setting of the air system introduces air into the tank body. If the air volume is insufficient, the desulfurization effect will quickly decrease. According to the load of the desulfurization system, the speed of the fan is adjusted through a frequency converter. Install an oxygen sensor at the back of the desulfurization system as a safety guarantee for controlling air intake. During normal operation, the remaining oxygen content in the outlet gas is 1.5-2.0%. If the oxygen content in biogas exceeds 1.75%, the fan speed will decrease. If it reaches 2.5%, the fan will stop. This value can be set.
循环泵设置备用泵,一个故障时可快速切换到另一个使用。
The circulating pump is equipped with a backup pump, which can quickly switch to another for use in case of a malfunction.
防爆系统的设置和生物脱硫的内部设计都是防爆设计。另外,在生物脱硫设备间内部装有防爆气体监测器,如果甲烷水平超过低爆炸极限的 25%(LEL),气体监测器将自动切断电源,打开防爆风扇,防止爆炸风险。
The safety settings of the explosion-proof system and the internal design of biological desulfurization are both explosion-proof designs. In addition, an explosion-proof gas monitor is installed inside the biological desulfurization equipment room. If the methane level exceeds 25% of the minimum explosion limit (LEL), the gas monitor will automatically cut off the power supply and turn on the explosion-proof fan to prevent explosion risk.
为了确保细菌的良好活性,使用热交换器和温度监测器来调节和控制系统温度。 PH计用于控制营养液的添加。例如,如果PH值低于设定值,则将新鲜的营养液和稀释水自动添加到脱硫塔中。同时,废液自动排出,液位达到平衡。
To ensure the good activity of bacteria, heat exchangers and temperature monitors are used to regulate and control the system temperature. The pH meter is used to control the addition of nutrient solution. For example, if the pH value is lower than the set value, fresh nutrient solution and dilution water will be automatically added to the desulfurization tower. At the same time, the waste liquid is automatically discharged and the liquid level reaches equilibrium.
通过计量泵(计量泵设计为一用一备)定期添加营养液。液位开关控制整体液位平衡。
Regularly add nutrient solution through a metering pump (designed as one in use and one backup). The liquid level switch controls the overall liquid level balance.